PROJECT: Retrofit Existing Boilers to Meet Low NOx Emissions Requirements

Three Kewanee boilers sit side-by-side below the thousands of shoppers that walk the floors above 365 days per year.  The boilers are needed to provide the heating and cooling for the shopping facility year round.  One of the boilers retrofitted, Kewanee Model KR88, a 350 HP firetube steam boiler, was retrofitted to meet the Bay Area Air Quality Management District’s Regulation 9 Rule 7.  This regulation required retrofit of all boilers with input capacities of 10,000,000 BTU/hr and greater.  The actual emissions test results are summarized as follows:

Actual Performance
NOx 21 ppm & CO 3 ppm

BAAQMD Reg. 9 Rule 7 Emissions Requirements
NOx 30 ppm & CO 400 ppm


The project involved new Power Flame Vector Burners and controls to upgrade the existing firetube boilers.  Two of the three boilers were retrofitted and the third boiler received new controls only. 
Power Flame Vector burners were selected for their industrial grade 3/16” steel plate construction, their compact yet heavy duty packaged design, simplified induced flue gas recirculation system, and the burner’s ability to produce emissions well below the requirements of the Bay Area Air Quality Management District.


The Hillsdale Mall boilers, modified by R.F MacDonald Co. field service technicians, operate well below the required emissions regulations. Our goal is not only to upgrade equipment to comply with air quality regulations, but to have the equipment operate substantially below the required emission limits. This provides the equipment owners and operators with the peace of mind that the equipment will operate reliably within the mandated emissions requirements for many years to come.    

 