Boiler Equipment Maintenance Plans
We offer a customizable Boiler Equipment Maintenance Plan to maintain optimum performance, improve system stability, extend equipment life, and minimize risk of a boiler system failure. By participating in the contracted service, your equipment will receive the necessary assessments, testing, and maintenance to fully support the routine and essential inspections. Ultimately, these services will enhance equipment safety, efficiency, and performance. At the end of the annual maintenance, the boiler will be closed and fitted with new high-quality gaskets. All findings will be properly documented.
Customize Your Maintenance Visit Schedule
- To accommodate your operational needs and availability, you can customize the frequency of onsite visits to be Monthly, Quarterly, Semi-Annual, or Annual. Each option entails different inspections and services associated with each visit, see what’s included in each plan below.
- ANNUAL
The Core Coverage option where preventive maintenance will be performed on a semi-annual basis. The inspections and tests listed below will be completed once a year.
Boiler Inspection and Cleaning with a Next Day Tune Up
Combustion and Controls
- Check/sign in with customer representative
- Wear required PPE
- Perform job safety audit
- Inspect all actuators & motors for abnormal operation
- Inspect all lights, indicators, & alarms for functionality
- Inspect & clean all burner strainers & filters
- Inspect atomizing media equipment
- Inspect boiler & burner components for wear Inspect burner flame pattern
- Inspect firing rate control
- Inspect flue, vent, stack, & outlet dampers
- Inspect fuel nozzles & fuel outlet orifices
- Inspect fuel train(s), regulator(s), & valves
- Inspect diffuser positioning
- Perform a pilot turndown test
- Perform leak test on pilot & fuel train(s)
- Test & reset combustion
- Test & verify firing rate control set points
- Test flame failure safety shutdown timing
- Test fuel train(s) interlocks
- Test high & low fuel temperature/pressure interlocks
- Inspect gauges, monitors, & indicators
- Inspect igniter for damage & wear
- Inspect inlet & outlet dampers
- Inspect instruments & equipment settings
- Inspect linkage, drive arms, & damper connections for wear
- Inspect main fuel safety shutoff & vent valves for leakage
- Inspect pilot & main fuel flame signal strength
- Inspect pilot line, regulators, & valves
- Inspect the blower motor operation
- Inspect the diffuser & burner components for ear
- Test atomizing medium interlocks & set points
- Test burner position interlocks
- Test combustion air proving switch
- Test damper position interlocks
- Test flame failure detection system for pilot & main fuel(s)
- Test operating & high limit control functionality
- Test trial for ignitions & full sequence timing
- (Add-on) Secondary fuel tune-up
Fireside
- Inspect boiler for visible signs of hot spots & discoloration
- Inspect attaching mechanisms & open all access doors
- Inspect fireside of boiler & clean debris or soot as required
- Inspect the refractory & insulation for wear
Waterside
- Drain boiler, open manholes & handholes for inspection
- Remove water column plugs, and flush level controls and piping as needed
- Inspect & flush waterside of boiler
- Inspect PV for cracks, visible corrosion & scale
- Inspect the feed water valve & controls for operation
- Open & inspect internals of low water cutoff equipment
- Test safety relief valves for proper operation (as requested); Blow down the gauge glass assembly
- Inspect & flush pressure control tree as needed
- Inspect blowdown valves & equipment for leakage & wear
- Inspect the safety relief valves for leakage
- Inspect water column & gauge glass
- Replace tubular glass and valve sets only. For flat glass applications replace glass and gasket only
- Perform a slow drain test on low water cutoff
- Test water column water level ports
- Turn boiler back over to customer
- The boiler room shall be left in the same clean condition as existed prior to start of the work
- Check/sign out with customer representative
- Upon completion of full testing, your field service representative will submit an engineering report for your review and records. The engineering report will summarize work completed, detail corrective actions required and recommended solutions. Your customer service representative will contact you regarding recommendations.
- QTRLY/SEMI-ANNUAL
The Principal Coverage option where preventive maintenance will be performed on a quarterly basis. The inspections and tests listed below will be completed three (3) times a year in addition to one (1) Annual Maintenance visit. The same features are also available with the Semi-Annual Maintenance option, but with (2) visits.
Boiler Inspection, testing, and fine-tuning of the fuel-to-air combustion curve(s) to maximize burner combustion efficiency.
Combustion and Controls
- Check/sign in with customer representative
- Wear required PPE
- Perform job safety audit
- Inspect all actuators & motors for abnormal operation
- Inspect all lights, indicators, & alarms for functionality
- Inspect atomizing media equipment
- Inspect boiler & burner components for wear
- Inspect burner flame pattern
- Inspect firing rate control
- Inspect flue, vent, stack, & outlet dampers operations
- Inspect fuel train(s), regulator(s), & valves
- Inspect gauges, monitors, & indicators
- Inspect igniter for damage & wear
- Inspect inlet & outlet dampers
- Inspect instruments & equipment settings
- Inspect linkage, drive arms, & damper connections for wear
- Inspect pilot & main fuel flame signal strength
- Inspect pilot line, regulators, & valves
- Inspect the blower motor operations
- Perform a pilot turndown test
- Perform leak test on pilot & fuel train(s)
- Test & reset combustion
- Test flame failure detection system for pilot & main fuel(s)
- (Add-on) Secondary fuel tune-up
Fireside
- Inspect boiler for visible signs of hot spots & discoloration
Waterside
- Blow down the gauge glass assembly
- Inspect blowdown valves & equipment for leakage & wear
- Inspect the safety relief valves for leakage
- Inspect the feed water valve & controls for operation
- Inspect water column & gauge glass for wear & etching
- Test water column water level ports
- Perform a slow drain test on low water cutoff
- Turn boiler back over to customer
- The boiler room shall be left in the same clean condition as existed prior to start of the work
- Check/sign out with customer representative
- Upon completion of full testing, your field service representative will submit an engineering report for your review and records. The engineering report will summarize work completed, detail corrective actions required and recommended solutions. Your customer service representative will contact you regarding recommendations
- MONTHLY
The Maximum Coverage option where preventive maintenance will be performed every month. The inspections and tests listed below will be completed eight (8) times a year in addition to one (1) Annual Maintenance visit and three (3) Quarterly Maintenance visits.
Boiler Inspection and fine-tuning of the fuel-to-air combustion curve(s) to maximize burner combustion efficiency.
Combustion and Controls
- Check/sign in with customer representative
- Wear required PPE
- Perform job safety audit
- Inspect all actuators & motors for abnormal operation
- Inspect atomizing media equipment
- Inspect boiler & burner components for wear
- Inspect burner flame pattern
- Inspect firing rate control
- Inspect flue inlet & outlets & draft dampers for operation
- Inspect fuel train(s), regulator(s), & valves
- Inspect gauges, monitors, & indicators
- Inspect inlet & outlet dampers
- Inspect instruments & equipment settings
- Inspect linkage, drive arms, & damper connections for wear
- Inspect pilot & main fuel flame signal strength
- Inspect pilot line, regulators, & valves
- Inspect the blower motor operations
- Test & reset combustion
- (Add-on) Secondary fuel tune-up
Fireside
- Inspect boiler for visible signs of hot spots & discoloration
Waterside
- Blow down the gauge glass assembly
- Inspect the safety relief valves for leakage
- Inspect the feed water valve & controls for operation
- Inspect water column & gauge glass for wear & etching
- Test water column water level ports
- Turn boiler back over to customer
- The boiler room shall be left in the same clean condition as existed prior to start of the work
- Check/sign out with customer representative.
- Upon completion of full testing, your field service representative will submit an engineering report for your review and records. The engineering report will summarize work completed, detail corrective actions required and recommended solutions. Your customer service representative will contact you regarding recommendations
- DA
Deaerator Tank Annual
- Drain and open tank for inspection
- Inspect internals (visually) for corrosion
- Inspect internals (visually) for possible component failure
- Remove plugs from equalizing lines
- Inspect water column & gauge glass
- Replace tubular glass and valve sets only. For flat glass applications replace glass and gasket only
- Open high and low level alarm float bowls
- Flush tank and control the lines
- Inspect and thoroughly clean feed pump suction strainers
- Inspect pump couplings for excessive wear
- Check the pump discharge pressure
- Inspect safety relief valves for leaks and replace as needed
- Inspect DA PRV station for proper operation
- Reassemble the deaerator tank
- Check pump motor amperage draws
- Reset pressure and temperature controls or obtain desired set point
- Record control settings and perform operational tests
- Assure that tank is operating properly and safety
- SOURCE TEST
Pre-Source Test Tune Up & STSB (Boiler will not need to shut down for this service)
- Check/sign in with customer representative
- Wear required PPE
- Perform job safety audit
- Inspect burner operation
- Inspect for fuel gas leaks
- Inspect boiler for any indications of new hot spots
- Check for leaks, noise, vibration, unusual conditions, etc
- Check operation and adjust low water and/or feed water pump controls
- Check and adjust combustion per permit requirements
- Work with source test company to perform source testing of boiler
- Turn boiler back over to customer
- The boiler room shall be left in the same clean condition as existed prior to start of the work
- Check/sign out with customer representative
- Upon completion of full testing, your field service representative will submit an engineering report for your review and records. The engineering report will summarize work completed, detail corrective actions required and recommended solutions. Your customer service representative will contact you regarding recommendations
- ...
Additional Notes
- Proposal price good for (30) thirty days
- Delivery of parts to be determined upon receipt of receipt of order or otherwise noted
- All work to be performed during normal working hours, Monday to Friday, 7am-4pm, night, weekend or holiday work is not included unless otherwise noted
- There is no asbestos or lead handling or removal covered in this proposal
- Permits such as OSHPD, air quality, or building permits are not included in this proposal
- R.F. MacDonald Co. is the exclusive Cleaver Brooks Factory parts and service representative for your area. Parts used in the above scope of work will meet or exceed Cleaver Brooks Specifications. Factory-trained technicians will perform all work
- This job covers only those items listed in the above scope of work
- If necessary customer will be provided a separate proposal for work required and not covered in the scope of work in this proposal
- Customer’s existing isolation valves must be able to hold
- Insulation by others unless noted otherwise
- Customer to provide sufficient load conditions for this proposal scope of work tune up
- Customer’s oil firing equipment must be in good operating condition
- Boiler must be offline, isolated and cold when technicians arrive on site to perform this proposal scope of work. If boiler is not ready for any reason such as, boiler not shut down, boiler too hot to work on, etc (Customer will be invoiced a crew mobilization charge, which is not included in this proposal)
- Boiler must be available when technicians arrive on site to perform this proposal scope of work. If boiler is not available for any reason (Customer will be invoiced a crew mobilization charge, which is not included in this proposal)
- During the performance of this proposal scope of work, any delays caused by anyone other than R.F. MacDonald Co. personnel may require proposal price adjustment
Membership Term Options
In addition to offering customizable options for the frequency of maintenance services, we also provide the ability to select the corresponding term duration, indicating the length of the membership contract. We’ve divided these options into four (4) tiers, each one coming with complimentary benefits added to the extended length.
5 YEARS
Recurring services and inspections for five years. Term benefits include:
- Fixed pricing for five (5) years
- Discounted payment options
- Two (2) free training classes at a local seminar
- Priority scheduling benefits
- (Add-on) Onsite Pump Training
3-4 YEARS
Recurring services and inspections for three and four years. Term benefits include:
- Fixed pricing for three (3) and four (4) years
- Discount payment options
- One (1) free training class at a local seminar
- Priority scheduling benefits
- (Add-on) Onsite Pump Training
1-2 YEARS
Recurring services and inspections for one and two years. Term benefits include:
- Discount payment options for (2) years only
- Priority scheduling benefits
- (Add-on) Onsite Pump Training
Discount Payment Options
4% Discount – Annual (1) Payments – 100% invoiced upon receipt of order
3% Discount – Semi-Annual (2) Payments – 50% upon receipt of order, followed by (1) six-month invoice
2% Discount – Quarterly (4) Payments – 25% upon receipt of order, followed by (3) quarterly invoices
Free Boiler Training
5 Year EMP = Two (2) free training classes at a local seminar
3-4 Year EMP = One (1) free training class at a local seminar
Why Should You Invest?
Routine Boiler and Pressure Vessel inspections are required by local jurisdictions. Typically, these critical inspections are required annually, but in some rare cases, they can be required bi-annually. The inspection frequency is determined by local laws and regulations. As such, Boiler and Pressure Vessel inspections are unavoidable and will result in a boiler and/or boiler system to be temporarily taken offline. The specific details involved to perform an annual inspection can be overwhelming for companies that do not have the resources to stay current with changing compliance regulations. As a result, it is beneficial and very common for companies to engage in knowledgeable technical resources who can easily navigate the inspection process. Outsourcing this responsibility to trained technicians can facilitate an expedient and successful approval by the local jurisdiction while enhancing your preventive maintenance objectives.
Under the Equipment Maintenance Plan, you can—
- Improve operational stability
- Improve burner combustion efficiency
- Improve boiler heat transfer efficiency
- Enhance safety and issue identification
- Reduce long-term repair cost
- Discounted parts quotes where needed
- Fixed labor erase inconvenience service fees
- Reduce annual inspection difficulties
- Priority access to technical expertise & service support
- Priority access to R.F. MacDonald Co. parts inventory
- Single-source responsibility for boiler system support
- Extend equipment life
Maintaining Your Equipment
Whether or not you choose to utilize our preventive maintenance program, we highly recommend that you take steps to ensure that your boiler equipment is protected. Additionally, we offer accredited training courses on boiler operations and mechanics, visit R.F. MacDonald Co. Training for more information. Below are some valuable tips to follow when being proactive on the condition of your boiler application.
Controls
Proper water levels, operating pressures, and control devices are critical to your boiler system’s performance. Carefully check gauge glass for cracks or erosion and inspect the float and switches. Check the operation of all limit switches and sequences of operation timing.
Burners
Remove, check and clean dampers, nozzles, electrodes, scanners, hoses, compressors, filters, diffusers, etc. for blockage and/or damage.
Refractory
Check for cracking. Unrepaired, even mirror cracks can reduce boiler efficiency and allow warping and damage to occur on vital metal surfaces.
Fireside
Cleaning out any detectable soot can reduce the efficiency of your boiler tubes, tube sheets, and furnace area. Replace fireside gaskets when closing the boiler.
Waterside
Drain, open and flush the entire waterside of the boiler. Remove all low water controls to clean and inspect piping. Flush makeup and/or feed water pump strainers and water column float chambers. Drain expansion tanks and remove all plugs in control piping. Inspect and re-install controls. Inspect for damage due to waterside leakage around handholes and manholes, gauge glass assemblies and other wet surfaces. Check gaskets for wear and tear.